INVESTIGATION OF THERMAL PERFORMANCE OF FINNED, WATER-PCM, DOUBLE TUBE HEAT RECOVERY
Autor: | Mohammed H. Mahmoud, Maathe A.Theeb, Ali S. Golam |
---|---|
Jazyk: | Arabic<br />English |
Rok vydání: | 2015 |
Předmět: | |
Zdroj: | Journal of Engineering and Sustainable Development, Vol 19, Iss 4 (2015) |
Druh dokumentu: | article |
ISSN: | 2520-0917 2520-0925 |
Popis: | In this work, focus is taken on developing a waste heat recovery system for capturing potential of exhaust heat from an air conditioner unit to be reused later. This system has the ability to store heat in phase change material (PCM) and then release it to a discharge water system when required. To achieve this goal, a Finned, Water-PCM, Double tube (FWD) system has been developed and tested. Different profiles of fins attached to the (FWD) system have been investigated for increasing the thermal conductivity of the PCM. These include using Circular Finned, Water-PCM, Double tube (CFWD) system; Longitudinal Finned, Water-PCM, Double tube (LFWD) system; Spiral Finned, Water-PCM, Double tube (SFWD) system; as well as; Without Fins, Water-PCM, Double tube (WFWD) system. An experimental test rig that attached to an air-conditioner unit has been built to include 32 tubes of the FWD systems for both vertical and horizontal layouts during charging and water discharging processes. Transient 3-D, numerical simulations using (ANSYS Fluent14.0 software) have been developed to predict the thermal behavior for all types of FWD systems under investigation. |
Databáze: | Directory of Open Access Journals |
Externí odkaz: |