Popis: |
The data of physicochemical control for the cooling water supply system of the Rivne Nuclear Power Plant (Ukraine), where water samples were monitored three times a day during 2022–2023. The pH, temperature, total dissolved salts, total hardness and total alkalinity were measured using standard methods. The differences in ϕ and ψ, Langelier saturation index (LSI) and Ryznar stability index (RSI), which characterise scaling and corrosive potential, were calculated The calculated values are ϕ - ψ: 0.29 (± 0.62), LSI: 1.51 (± 0.39), and RSI 5.74 (± 0.69). According to the scaling and corrosive classification, the water is characterised as susceptible to scale formation. Moreover, to the Pearson correlation coefficient (ρ), there is a very strong relationship ρ = −0.9635 between LSI and RSI, a weak relationship ρ = −0.2370 between ϕ - ψ and RSI, and ρ = −0.2997 between ϕ - ψ and LSI. |