Transient Studies in Large Offshore Wind Farms Employing Detailed Circuit Breaker Representation

Autor: Jesper Hjerrild, Claus Leth Bak, Jakob Glasdam
Jazyk: angličtina
Rok vydání: 2012
Předmět:
Zdroj: Energies, Vol 5, Iss 7, Pp 2214-2231 (2012)
Druh dokumentu: article
ISSN: 1996-1073
DOI: 10.3390/en5072214
Popis: Switching overvoltages (SOV) are considered a possible source of component failures experienced in existing offshore wind farms (OWFs). The inclusion of sufficiently accurate and validated models of the main electrical components in the OWF in the simulation tool is therefore an important issue in order to ensure reliable switching operations. Transient measurement results in an OWF are compared with simulation results in PSCAD EMTDC and DigSILENT Power Factory. A user-defined model of the vacuum circuit breaker (VCB) is included in both tools, capable of simulating multiple prestrikes during the closing operation. An analysis of the switching transients that might occur in OWFs will be made on the basis of the validated model, and the importance of the inclusion of a sufficiently accurate representation of the VCB in the simulation tool will be described. The inclusion of the VCB model in PSCAD greatly improves the simulation results, whereas little improvement is found in DigSILENT. Based on the transient study it is found that the simulated SOV can be up to 60% higher at the sending end when using the detailed VCB representation compared to the built-in switch, which emphasises the need for accurate representation of the VCB for energisation studies.
Databáze: Directory of Open Access Journals