Influence of generator excitation system on generator under-impedance protection
Autor: | Sučević Nikola, Lukić Sanja |
---|---|
Jazyk: | English<br />Serbian |
Rok vydání: | 2019 |
Předmět: | |
Zdroj: | Zbornik Radova: Elektrotehnički Institut "Nikola Tesla", Vol 29, Iss 29, Pp 57-70 (2019) |
Druh dokumentu: | article |
ISSN: | 0350-8528 2406-1212 |
Popis: | This paper analyses the influence of the operation of the automatic voltage regulator and the stator maximum current limiter in the excitation system on the operation of under-impedance generator protection, with the focus on zone 2 of the protection function. The paper analyses the response of the automatic voltage regulator to a given disturbance in the transmission network and observes its influence on the trajectory of the operating point measured by the under-impedance generator protection. Based on the simulation results, the adequacy of the selected under-impedance protection settings was evaluated. Network modelling and analysis were performed in the DlgSILENT PowerFactory software package. |