Effect of square wings in multiple square perforated twisted tapes on fluid flow and heat transfer of heat exchanger tube

Autor: Amar Raj Singh Suri, Anil Kumar, Rajesh Maithani
Jazyk: angličtina
Rok vydání: 2017
Předmět:
Zdroj: Case Studies in Thermal Engineering, Vol 10, Iss C, Pp 28-43 (2017)
Druh dokumentu: article
ISSN: 2214-157X
DOI: 10.1016/j.csite.2017.03.002
Popis: This work presents, an experimental study on Nusselt number (Nurs) and friction factor (frs) of heat exchanger circular tube fitted with multiple square perforated with square wing twisted tape inserts. The experimental determination encompassed the geometrical parameters namely, wing depth ratio (Wd/WT) of 0.042–0.167, perforation width ratio (a/WT) of 0.250, twist ratio (TL/WT) of 2.5, and number of twisted tapes (NT) of 4.0. The effect of multiple square perforated twisted tape with square wing has been investigated for the range of Reynolds number (Ren) varied from 5000 to 27,000. The maximum enhancement in Nurs and frs is observed to be 6.96 and 8.34 times of that of the plain circular tube, respectively. Correlations of Nurs, frs and ηp are established in term of Ren and geometrical parameters of wings twisted tape which can be used to predict the values of Nurs, frs and ηp with considerably good accuracy.
Databáze: Directory of Open Access Journals