Autor: |
Cédric Dananché, Marie-Paule Gustin, Pierre Cassier, Sophie Tiphaine Loeffert, Michel Thibaudon, Thomas Bénet, Philippe Vanhems |
Jazyk: |
angličtina |
Rok vydání: |
2017 |
Předmět: |
|
Zdroj: |
PLoS ONE, Vol 12, Iss 5, p e0177263 (2017) |
Druh dokumentu: |
article |
ISSN: |
1932-6203 |
DOI: |
10.1371/journal.pone.0177263 |
Popis: |
The main purpose was to validate the use of outdoor-indoor volumetric impaction sampler with Hirst-type spore traps (HTSTs) to continuously monitor fungal load in order to prevent invasive fungal infections during major structural work in hospital settings. For 4 weeks, outdoor fungal loads were quantified continuously by 3 HTSTs. Indoor air was sampled by both HTST and viable impaction sampler. Results were expressed as particles/m3 (HTST) or colony-forming units (CFU)/m3 (biocollector). Paired comparisons by day were made with Wilcoxon's paired signed-rank test or paired Student's t-test as appropriate. Paired airborne spore levels were correlated 2 by 2, after log-transformation with Pearson's cross-correlation. Concordance was calculated with kappa coefficient (κ). Median total fungal loads (TFLs) sampled by the 3 outdoor HTSTs were 3,025.0, 3,287.5 and 3,625.0 particles/m3 (P = 0.6, 0.6 and 0.3).-Concordance between Aspergillaceae fungal loads (AFLs, including Aspergillus spp. + Penicillium spp.) was low (κ = 0.2). A low positive correlation was found between TFLs sampled with outdoor HTST and indoor HTST with applying a 4-hour time lag, r = 0.30, 95% CI (0.23-0.43), P |