Popis: | The article presents the results of comparative investigations of partial discharges in two insulation systems; aramid-enhanced cellulose paper-mineral oil, and pure cellulose paper-mineral oil. Partial discharges were investigated in a diagonal electric field with vertical and horizontal components. This field is treated as the most dangerous for insulation. The research was carried out on Nomex® 910 paper and cellulose paper samples, each paper being 0.25 mm thick. Samples of the two materials were tested at four levels of moisture. The inception voltage of partial discharges of all samples tested decreased as their moisture content increases. It was also proved that Nomex® 910 has a significantly higher partial discharge inception voltage than the cellulose paper, although this difference decreased with increasing moisture content. |