Ground Return Current Behaviour in High Voltage Alternating Current Insulated Cables

Autor: Roberto Benato, Sebastian Dambone Sessa, Fabio Guglielmi, Ertugrul Partal, Nasser Tleis
Jazyk: angličtina
Rok vydání: 2014
Předmět:
Zdroj: Energies, Vol 7, Iss 12, Pp 8116-8131 (2014)
Druh dokumentu: article
ISSN: 1996-1073
DOI: 10.3390/en7128116
Popis: The knowledge of ground return current in fault occurrence plays a key role in the dimensioning of the earthing grid of substations and of cable sealing end compounds, in the computation of rise of earth potential at substation sites and in electromagnetic interference (EMI) on neighbouring parallel metallic conductors (pipes, handrails, etc.). Moreover, the ground return current evaluation is also important in steady-state regime since this stray current can be responsible for EMI and also for alternating current (AC) corrosion. In fault situations and under some assumptions, the ground return current value at a substation site can be computed by means of k-factors. The paper shows that these simplified and approximated approaches have a lot of limitations and only multiconductor analysis can show the ground return current behaviour along the cable (not only the two end values) both in steady-state regime and in short circuit occurrence (e.g., phase-to-ground and phase-to-phase-to-ground). Multiconductor cell analysis (MCA) considers the cable system in its real asymmetry without simplified and approximated hypotheses. The sensitivity of ground return current on circuit parameters (cross-bonding box resistances, substation earthing resistances, soil resistivity) is presented in the paper.
Databáze: Directory of Open Access Journals