Speed distribution in the exhaust diffuser of the air fan

Autor: Gherghe Ion, Cioclea Doru, Rădoi Florin, Chiuzan Emeric, Drăgoescu Răzvan
Jazyk: English<br />French
Rok vydání: 2022
Předmět:
Zdroj: MATEC Web of Conferences, Vol 354, p 00027 (2022)
Druh dokumentu: article
ISSN: 2261-236X
DOI: 10.1051/matecconf/202235400027
Popis: A perfect connection between the column and the fan is that which ensures an air inlet in the fan, evenly distributed, over the entire surface of the suction mouth and an air outlet from the fan outlet made in a way that allows the full use of developed pressure. For both suction and exhaust, fans must be equipped with a device/diffuser. When the fan discharges freely into the atmosphere without any connection, a loss equivalent to 50% of the average dynamic pressure at the discharge port occurs. If the fan discharges into a speaker, the loss depends on its angle. At a peak angle of 30° corresponds to a loss of ≈ 25% of the average dynamic pressure in the discharge mouth, and to reduce air vortices the speakers must be built at an angle of inclination to vertical or horizontal between 12- 15°, in order to reduce the aerodynamic resistances. The paper will present the speed field distribution of an axial fan located on a circular duct, provided on the air discharge side with a diffuser with a length of 1.5 m, at an angle of inclination to the vertical or horizontal of 12°.