МОДЕЛЮВАННЯ НЕПОВНОФАЗНИХ РЕЖИМІВ РОБОТИ ЕЛЕКТРИЧНИХ МЕРЕЖ НАПРУГОЮ 110 КВ З НЕЛІНІЙНИМИ ЕЛЕМЕНТАМИ
Jazyk: | ukrajinština |
---|---|
Rok vydání: | 2021 |
Předmět: | |
Zdroj: | Технічні науки та технології; № 2(24) (2021): Технічні науки та технології; 171-178 Technical sciences and technology; No. 2(24) (2021): Technical sciences and technologies; 171-178 Технические науки и технологии; № 2(24) (2021): Технічні науки та технології; 171-178 |
ISSN: | 2411-5363 2519-4569 |
Popis: | In electric circuits with a series or parallel connection of a nonlinear inductor and a capacitive element with a change in voltage or current of the power supply, the phenomenon of ferroresonance is observed. Ferroresonance is a complex nonlinear electrical phenomenon, the problem of protection against which still remains unresolved. In this paper, the main causes of ferroresonant overvoltages in electrical networks of different voltage classes were analyzed. The analysis revealed that the problem of protection against ferroresonant overvoltages is quite relevant. The amplitude of overvoltages in these processes can be (2 ÷ 6) Uf. These overvoltages are the most dangerous of all their types that can be in existing high-voltage networks. The main cause of ferroresonance in voltage transformers is switching in idle mode and incomplete phase modes of operation of the electrical network. In this paper, the conditions of ferroresonance processes in 110 kV electric networks are carefully investigated and a model created in the circuit design package Matlab Simulink is proposed. With the help of the created model the formation of ferroresonant overvoltages in the 110 kV network at incomplete phase regimes at different line lengths was investigated. According to the simulation results, the overvoltages in the network reach (2 ÷ 6) Uf. The dependence of the multiplicity of ferroresonant overvoltages on the line length and on the phase at the moment of inclusion is investigated too. The area of existence of dangerous overvoltages, with a multiplicity up to 6Uf, connected with ferroresonance, is determined by the lengths of the power transmission line with a voltage of 110 kV. The most dangerous overvoltages occur at lengths of power lines from 5 to 70 km. У роботі досліджено умови виникнення ферорезонансних процесів в електричних мережах напругою 110 кВ шляхом моделювання у схемотехнічному пакеті Matlab Simulink. Запропонована в роботі модель дозволяє досліджувати умови виникнення ферорезонансних перенапруг в електричних мережах напругою 110 кВ та, на основі отриманих даних розробляти заходи, направлені на усунення причин та мінімізацію наслідків ферорезонансних перенапруг. |
Databáze: | OpenAIRE |
Externí odkaz: |