[Influence of local air suction on the density of air-borne bacteria during cementation of alloplasties]

Autor: T P, Enggaard, F, Møller-Larsen
Rok vydání: 1997
Předmět:
Zdroj: Ugeskrift for laeger. 159(7)
ISSN: 0041-5782
Popis: At joint replacement operations local air suction is used to reduce the air pollution from organic solvents in the operation theatre during insertion of cement and prosthesis. In order to find out whether the local suction in an ultraclean-air operation theatre with laminar airflow influenced the number of colony forming units (cfu) of bacterial in vicinity of the wound, one m3 of air was sampled 20 cm and one metre from the wound before, during and after use of local suction during insertion of cement and prosthesis using a Sartorius membrane filter sampler. There was no significant difference between the groups in the numbers of cfu of bacteria found. It is concluded that use of local air suction over the operative area while cementing hip prosthesis does not affect the number of bacteria in the vicinity of the operation.