International Compressor Engineering Conference |
Popis: |
Rising cooling needs for the residential and commercial air conditioning sectors and the requirement of higher SEER values increased the focus on energy-efficient part load performance. Although several studies exist on the topic of capacity modulation, there is no comprehensive study that compares different modulation strategies in the same experimental facility. In a first step, this paper aims to experimentally compare two different capacity controls for scroll compressors (single speed vs two-stage compressor) using the same R410A water ethylene glycol (WEG) chiller having a nominal cooling capacity of 8kW. The tests were conducted according to AHRI Standard 551/591 (2018). The Integrated Part Load Value (IPLV.SI) was used to fairly compare all these capacity modulation strategies. Based on the experimental results, the difference in the order of 8% in IPLV.SI is found. While both compressors showed comparable capacities and COPs at the higher modulation conditions, two stage compressor has better COP at the lower condition because of its ability to operate at a lower stage and better meet the required load. |