Methods to Minimize Zero-Missing Phenomenon
Autor: | Martin Randrup Knardrupgard, Claus Leth Bak, Filipe Miguel Faria da Silva, Unnur Stella Gudmundsdottir, W. Wiechowski |
---|---|
Jazyk: | angličtina |
Rok vydání: | 2010 |
Předmět: |
Shunt Reactor
Engineering business.industry Electrical engineering High-voltage cable Energy Engineering and Power Technology Transmission system AC power law.invention Level-crossing problems Power Cables Capacitor law AC Circuit Breaker Phenomenon Switching Transients Electrical and Electronic Engineering Resistor business Circuit breaker Shunt (electrical) |
Zdroj: | da Silva, F M F, Bak, C L, Gudmundsdottir, U S, Wiechowski, W & Knardrupgård, M R 2010, ' Methods to Minimize Zero-Missing Phenomenon ', I E E E Transactions on Power Delivery, vol. 25, no. 4, pp. 2923-2930 . https://doi.org/10.1109/TPWRD.2010.2045010 |
Popis: | With the increasing use of high-voltage AC cables at transmission levels, phenomena such as current zero-missing start to appear more often in transmission systems. Zero-missing phenomenon can occur when energizing cable lines with shunt reactors. This may considerably delay the opening of the circuit breaker, leaving the system unprotected and vulnerable to failures. Methods to prevent zero-missing phenomenon are still being studied and compared in order to identify effective countermeasures. This paper contributes to these efforts, by presenting several countermeasures that can be applied to reduce the hazards of zero-missing phenomenon. The authors discovered that this phenomenon can be eliminated, merely by using an extra circuit breaker or a pre-insertion resistor. |