Techno-Economic Performance Analysis of a 40.1 kWp Grid-Connected Photovoltaic (GCPV) System after Eight Years of Energy Generation: A Case Study for Tochigi, Japan
Autor: | Ghoname Abdullah, Hidekazu Nishimura |
---|---|
Rok vydání: | 2021 |
Předmět: |
Feed-In-Tariff (FIT)
020209 energy Geography Planning and Development TJ807-830 solar irradiation data 02 engineering and technology 010501 environmental sciences Management Monitoring Policy and Law TD194-195 01 natural sciences Renewable energy sources Automotive engineering solar energy in Japan 0202 electrical engineering electronic engineering information engineering GE1-350 0105 earth and related environmental sciences Environmental effects of industries and plants Renewable Energy Sustainability and the Environment business.industry Photovoltaic system Grid Power (physics) Environmental sciences photovoltaic system Electricity generation Capacity utilization Environmental science Inverter Electricity business Energy (signal processing) |
Zdroj: | Sustainability Volume 13 Issue 14 Sustainability, Vol 13, Iss 7680, p 7680 (2021) |
ISSN: | 2071-1050 |
DOI: | 10.3390/su13147680 |
Popis: | In this paper, the grid-connected photovoltaic system in Tochigi prefecture, Japan, is presented, and its technical and economic performance after eight years is evaluated. The system has a peak power of 40.1 kWp and has been in operation since 2012. The entire electricity generated by the system was fed into the state grid. The system is suitably monitored for one year (2019) and analyzed using the parameters developed and defined in the standard IEC 61724-1 by the International Electrotechnical Commission. The system’s different parameters included array yield, final yield, capacity utilization factor, and performance ratio of the system. An analytical model with solar irradiation obtained from Power Data Access Viewer was developed to investigate and evaluate the efficiency of the system monthly and annual energy generation by comparing the simulated and measured energy acquired from the inverter. A positive linear relationship is observed between solar irradiation data obtained from Power Data Access Viewer and the grid-connected photovoltaic system energy injected into the utility grid. While an annual total of 48,521 kWh of energy was expected to be generated, 38,071 kWh was generated and injected into the utility in 2019. This study also introduces and explains the mechanism of the Feed-In-Tariff system in Japan. The performance of the grid-connected photovoltaic system under this study was compared with that of other systems installed across the globe. |
Databáze: | OpenAIRE |
Externí odkaz: |