Precision loss measurement of reactive compensation components by sampling voltage and current
Autor: | Henrik Badura, Enrico Mohns, Esa-Pekka Suomalainen, S. Fricke, Jari Hällström |
---|---|
Jazyk: | angličtina |
Rok vydání: | 2016 |
Předmět: |
Engineering
02 engineering and technology Power Measurements law.invention Compensation (engineering) Sampling (signal processing) law Precision Measurements Reactor losses 0202 electrical engineering electronic engineering information engineering Electronic engineering ta114 ta213 business.industry System of measurement 020208 electrical & electronic engineering Electrical engineering Uncertainty High voltage Phantom power Metrology Capacitor Losses Capacitor business Loss compensation Voltage |
Zdroj: | Mohns, E, Hällström, J, Suomalainen, E-P, Badura, H & Fricke, S 2016, Precision loss measurement of reactive compensation components by sampling voltage and current . in Precision Electromagnetic Measurements (CPEM 2016), 2016 Conference on . IEEE Institute of Electrical and Electronic Engineers, pp. 1-3, Conference on Precision Electromagnetic Measurements, CPEM 2016, Ottawa, Canada, 10/07/16 . https://doi.org/10.1109/CPEM.2016.7540545 |
Popis: | This paper describes the setup of sampling-based high voltage measuring systems for reactive compensation components recently developed at VTT and PTB. First measurements show an agreement within 10−4 between both measuring systems. Both a phantom power source emulating reactors and capacitors with adjustable losses, and a set of real reactive components were measured. Measurements were performed with stable 53 Hz frequency and variable 50 Hz power frequency. The measuring systems are developed within the frame of the European project “ELPOW — Metrology for the Electrical Power Industry”. |
Databáze: | OpenAIRE |
Externí odkaz: |