Autor: |
Mhm Mart Grooten, Fla Frank Ganzevles, H Hagens, van der Cwm Cees Geld |
Rok vydání: |
2007 |
Předmět: |
|
Zdroj: |
Applied Thermal Engineering, 27(14-15), 2426-2434. Elsevier |
ISSN: |
1359-4311 |
DOI: |
10.1016/j.applthermaleng.2007.03.004 |
Popis: |
This paper presents measurements and predictions of a heat pipe-equipped heat exchanger with two filling ratios of R134a, 19% and 59%. The length of the heat pipe, or rather thermosyphon, is long (1.5 m) as compared to its diameter (16 mm). The airflow rate varied from 0.4 to 2.0 kg/s. The temperatures at the evaporator side of the heat pipe varied from 40 to 70 °C and at the condenser part from 20 to 50 °C. The measured performance of the heat pipe has been compared with predictions of two pool boiling models and two filmwise condensation models. A good agreement is found. This study demonstrates that a heat pipe equipped heat exchanger is a good alternative for air–air exchangers in process conditions when air–water cooling is impossible, typically in warmer countries. |