A method for calculating the parameters of the sine filter of the frequency converter, taking into account the criterion of starting current limitation and pulse-width modulation frequency
Autor: | Oleksandr Plakhtii, Denys Hordiienko, Volodymyr Nerubatskyi, Vasyl Ravluyk, Serhii Mykhalkiv |
---|---|
Jazyk: | angličtina |
Rok vydání: | 2021 |
Předmět: |
Computer science
Energy Engineering and Power Technology power sources LC circuit Industrial and Manufacturing Engineering Control theory Management of Technology and Innovation lcsh:Technology (General) lcsh:Industry Electrical and Electronic Engineering Oscilloscope self-commutated voltage inverter Total harmonic distortion sine filter Applied Mathematics Mechanical Engineering power quality Filter capacitor Computer Science Applications Control and Systems Engineering Filter (video) Harmonics lcsh:T1-995 lcsh:HD2321-4730.9 total harmonic distortion Frequency modulation Pulse-width modulation |
Zdroj: | Eastern-European Journal of Enterprise Technologies, Vol 1, Iss 8 (109), Pp 6-16 (2021) |
ISSN: | 1729-4061 1729-3774 |
Popis: | An analysis of the method for ensuring the sinusoidality of the output voltage in power generation systems with self-commutated voltage inverters under the requirements of the international standard IEEE-519 is presented. In a number of programs, especially low-power generation systems, a low-cost solution is needed to provide the sinusoidal waveform of the output voltage with the total harmonic distortion of 5%. This solution is to use two-level voltage inverters with an output sine LC filter. However, the feature of the sine filter with the frequency converter is that the PWM frequency affects the spectrum of higher harmonics of the output voltage. In addition, there is the starting current of the filter capacitor, which can disable the power switches of the voltage inverter. The developed method for calculating the values of the LC filter with the two-level voltage inverter in the PWM mode is presented meeting the requirements of the international standard IEEE-519, taking into account the modulation frequency and limitation of the starting current of the filter capacitor. To confirm the required quality of the output voltage of the two-level voltage inverter with the sine filter, an appropriate simulation model was created in the Matlab/Simulink computer simulation environment. The oscillograms and harmonic analysis of the input and output voltages of the sine filter, which showed the total harmonic distortion of 1.88%, are presented. A physical prototype of the investigated system was created on the basis of a 5.5kW OVEN PChV203-5K5-V frequency converter (Ukraine). Using the SIGLENT SDS1104X-E oscilloscope (China), the real waveform and the results of the harmonic analysis of the sine filter output voltage, confirming the implementation of the necessary sinusoidality criteria, were obtained |
Databáze: | OpenAIRE |