Adsorption-compression cascade cycles: An experimental study

Autor: Salvatore Vasta, Davide La Rosa, Walter Mittelbach, Valeria Palomba
Rok vydání: 2018
Předmět:
Zdroj: Energy conversion and management 156 (2018): 365–375. doi:10.1016/j.enconman.2017.11.061
info:cnr-pdr/source/autori:Salvatore Vasta, Valeria Palomba,Davide La Rosa, Walter Mittelbach/titolo:Adsorption-compression cascade cycles: An experimental study/doi:10.1016%2Fj.enconman.2017.11.061/rivista:Energy conversion and management/anno:2018/pagina_da:365/pagina_a:375/intervallo_pagine:365–375/volume:156
ISSN: 0196-8904
DOI: 10.1016/j.enconman.2017.11.061
Popis: In this paper the experimental testing of a cascade chiller composed of an adsorption unit and a vapour compression unit is reported. The operation of the cascade under realistic operating conditions, differing for the temperature of the heat source available and the environmental temperature is analysed. A comparison was made between the application of the cascade and a vapour compression chiller only for air conditioning applications. According to the heat source temperatures, an increase in the electric COP of the system ranging from 25% to 50% was measured, with a maximum value of 8. An optimization of the system was subsequently proposed, by evaluating different adsorbent materials and refrigerants through the use of thermodynamic models. The theoretical study revealed that a performance up to 110% higher with respect to traditional chillers could be obtained if the cascade was used in refrigeration applications.
Databáze: OpenAIRE