Using footwarmers in offices for thermal comfort and energy savings
Autor: | Fred Bauman, Edward Arens, Marc Fountain, Darryl Dickerhoff, David Fannon, Margaret Pigman, Mallory Taub, Wilmer Pasut, Yongchao Zhai, Hui Zhang |
---|---|
Rok vydání: | 2015 |
Předmět: |
Engineering
Footwarmer Thermal comfort Heating setpoint HVAC energy savings Personal comfort system Civil and Structural Engineering Building and Construction Mechanical Engineering Electrical and Electronic Engineering Automotive engineering Setpoint footwarmer Architecture personal comfort system Simulation Settore ING-IND/11 - Fisica Tecnica Ambientale business.industry Set point Heating energy Plug load business Energy (signal processing) heating setpoint |
Zdroj: | Zhang, Hui; Arens, Edward; Taub, Mallory; Dickerhoff, Darryl; Bauman, Fred; Fountaint, Marc; et al.(2015). Using Footwarmers in Offices for Thermal Comfort and Energy Savings. Energy and Buildings. doi: 10.1016/j.enbuild.2015.06.086. UC Berkeley: Center for the Built Environment. Retrieved from: http://www.escholarship.org/uc/item/3cf6268m |
ISSN: | 0378-7788 |
DOI: | 10.1016/j.enbuild.2015.06.086 |
Popis: | An office equipped with personal footwarmers was maintained at cooler-than-normal indoor temperatures in the winter, producing great energy savings. The occupants’ thermal comfort was not affected. The footwarmers provide individual heating control over a segment of the body that most strongly influences comfort perception when one is cool overall. If cooler ambient indoor temperatures could be made comfortable, savings in central heating energy would be possible. During a six-month winter period in Berkeley California, knowledge workers with low-energy footwarmers experienced a lowering of room heating set point from 21.1 °C (70 °F) to 18.9 °C (66 °F). Surveys showed equal thermal comfort in the original ‘higher heating setpoint no-footwarmer’ condition and the ‘lower heating set point plus occupant-controllable footwarmer’ condition. Heating energy was closely monitored throughout. It dropped 38–75% depending on the setpoint reduction and outdoor conditions. The added plug load energy from the low-energy footwarmers was much less than the central heating energy saved by lowering the heating set point (3–21 W vs 500–700 W average power per occupant during occupied hours). A few subjects had ergonomic issues with the particular footwarmers used, so usage was not universal. Additional foot- and leg-warmer design options would help. |
Databáze: | OpenAIRE |
Externí odkaz: |