Experimental Study on the Fire Performance of Tubular Steel Columns with Membrane Protections for Prefabricated and Modular Steel Construction
Autor: | Lei Peng, Yang Zhou, Xin Zhang, Tian-xiao Ni, Yi-liang Huang, Zhao-peng Ni |
---|---|
Rok vydání: | 2018 |
Předmět: |
Fire-resistance rating
Materials science Poison control 020101 civil engineering 02 engineering and technology lcsh:Technology Article axial load 0201 civil engineering Prefabrication hollow structural section (HSS) chemistry.chemical_compound Thermal insulation Fire protection General Materials Science Composite material lcsh:Microscopy lcsh:QC120-168.85 steel tubular column lcsh:QH201-278.5 business.industry lcsh:T 021001 nanoscience & nanotechnology Fire performance prefabricated and modular construction membrane protection chemistry lcsh:TA1-2040 Calcium silicate lcsh:Descriptive and experimental mechanics lcsh:Electrical engineering. Electronics. Nuclear engineering 0210 nano-technology business lcsh:Engineering (General). Civil engineering (General) Layer (electronics) lcsh:TK1-9971 |
Zdroj: | Materials Materials; Volume 11; Issue 3; Pages: 437 Materials, Vol 11, Iss 3, p 437 (2018) |
ISSN: | 1996-1944 |
Popis: | Experimental research was conducted to study the fire resistance of steel tubular columns used in prefabricated and modular construction. In order to achieve high-efficient prefabrication and fast on-site installation, membrane protections using board products and thermal insulation blankets are adopted as the favorable protection method. Three protected tubular columns were tested in a full-scale column furnace with axial load applied. The study variables were different membranes, including fiber reinforced calcium silicate (FRCS) boards, rock wool and aluminum silica (Fiberfrax) insulations. The results suggest that one layer of 12 mm FRCS board with rock wool insulation has insufficient fire protection. However, steel columns protected with two layers of 12 mm FRCS boards with insulation appeared to have good fire resistances and could achieve a fire resistance rating as high as 2.5~3.0 h. |
Databáze: | OpenAIRE |
Externí odkaz: | |
Nepřihlášeným uživatelům se plný text nezobrazuje | K zobrazení výsledku je třeba se přihlásit. |