Uベンドを有する二重管形凝縮器に関する研究 非共沸混合冷媒R114/R113による実験
Jazyk: | japonština |
---|---|
Rok vydání: | 1994 |
Předmět: |
Mass transfer coefficient
Pressure drop Materials science Critical heat flux Physics::Instrumentation and Detectors Mechanical Engineering Heat transfer enhancement Condensation U-Bend Double Tube Thermodynamics Heat transfer coefficient Condensed Matter Physics Pressure Drop Mass transfer Heat transfer Heat Transfer Enhancement Condenser Nonazeotropic Refrigerant Mixture Mass Transfer |
Zdroj: | 日本機械学会論文集 B編 = Transactions of the Japan Society of Mechanical Engineers Series B. 60(575):2472-2478 |
ISSN: | 0387-5016 |
Popis: | Local heat transfer and pressure drop measurements were made during condensation of a nonazeotropic refrigerant mixture R114/R113 in the annulus of a double-tube coil consisting of four straight sections and three U-bends. The inner tube was a corrugated tube having soldered wire fins. The vapor phase mass transfer coefficient exhibited a sawtooth behavior, with those of the U-bends larger than those of the straight sections. The frictional pressure gradient data agreed well with a previously developed empirical equation for the condensation of pure refrigerants. A prediction method for the condensation heat transfer rate was proposed on the basis of the correlations of the vapor phase mass transfer coefficient and heat transfer coefficient of the condensate film. The heat transfer data were correlated by the present prediction method to a mean absolute deviation of 12.9%. |