A Novel PSOS-CGSA Method for State Estimation in Unbalanced DG-Integrated Distribution Systems
Autor: | Jordan Radosavljević, M.R. Elkadeem, Zia Ullah, Shaorong Wang |
---|---|
Rok vydání: | 2020 |
Předmět: |
Variables
General Computer Science Computer science 020209 energy media_common.quotation_subject unbalanced distribution system metaheuristic optimization General Engineering Chaotic Control variable Particle swarm optimization 02 engineering and technology Hybrid algorithm Measure (mathematics) Acceleration Control theory 0202 electrical engineering electronic engineering information engineering 020201 artificial intelligence & image processing General Materials Science state estimation lcsh:Electrical engineering. Electronics. Nuclear engineering State (computer science) Hybrid intelligent algorithm lcsh:TK1-9971 media_common |
Zdroj: | IEEE Access, Vol 8, Pp 113219-113229 (2020) |
ISSN: | 2169-3536 |
DOI: | 10.1109/access.2020.3003521 |
Popis: | This paper proposes a novel optimization method, namely, hybrid PSOS-CGSA for state estimation in three-phase unbalanced DG-integrated distribution systems. The distribution system state estimation (DSSE) is formulated as a nonlinear optimization problem with constraints where loads and DG outputs are considered as the control variables, while real-time measurements are treated as dependent variables. The proposed DSSE model estimates the loads and DG outputs at each bus by minimizing the difference between the measure and calculated values of the variables monitored in real-time. A novel hybrid algorithm of particle swarm optimization with sigmoid-based acceleration coefficients and chaotic gravitational search algorithm (PSOS-CGSA) is proposed and applied for the DG-integrated DSSE. The feasibility of the proposed approach is verified on the IEEE 13-bus test system, the IEEE 37-bus test system, and the IEEE 123-bus test system. These simulations show that the proposed DSSE model provides reliable and accurate state estimation of DG-integrated distribution systems with a very limited number of real-time measurements at the source substation. The results obtained by proposed hybrid PSOS-CGSA are evaluated by comparing with other methods under the same test conditions, and the obtained results demonstrate the merits of the proposed scheme. |
Databáze: | OpenAIRE |
Externí odkaz: |