Popis: |
The capacity of a power network to host new distributed generation units and non-linear loads like PVs and EVs can be studied from different aspects, such as over voltage, unbalance and harmonic distortion. This paper proposes a new approach for estimating a safe hosting capacity in terms of harmonic distortion, considering standard limits for harmonic voltages and currents. It is shown that triple harmonics and even harmonics are the harmonic orders that determine the total hosting capacity. |