Hybrid Liquid Desiccant System Design and Operation Under High Latent Load Conditions in Taiwan
Autor: | Laura Alonso, Andoni Diaz de Mendibil, Xabier Peña, Khaled Gommed, Juan Prieto |
---|---|
Jazyk: | angličtina |
Rok vydání: | 2018 |
Předmět: |
Experimental performance
Continuous operation business.industry 020209 energy Mechanical Engineering Humidity 02 engineering and technology Building and Construction 7. Clean energy HVAC Falling-film Automotive engineering 020401 chemical engineering Air conditioning Hybrid system 0202 electrical engineering electronic engineering information engineering Liquid desiccant Systems design Environmental science 0204 chemical engineering business Liquid desiccant system Efficient energy use |
Popis: | Hybrid Liquid Desiccant systems (HLDS) combine the liquid desiccant technology for dehumidification of air with conventional compression cycle technology for cooling. They are an alternative to conventional compression cooling systems, being more efficient and offering the possibility of independently control temperature and humidity. In this paper the design and operation of a HLDS is presented, for the air conditioning of a high latent load application with high ambient humidity levels. An analysis of the daily evolution of the performance of the system under different environmental conditions has been included. The innovative demonstration unit placed in Taiwan, in continuous operation since November 2015, achieved Energy efficiency Ratios (EER) up to 4.6. The authors would like to thank the support of the project “nanoCOOL” funded by the Seventh Framework Programme FP7/2007-2013, Project No. 314701. |
Databáze: | OpenAIRE |