The use of non-metal materials in the filler units of cooling towers with circulating water supply system
Autor: | Ilnur N. Madyshev, Andrey V. Dmitriev, Aliya I. Khafizova |
---|---|
Jazyk: | angličtina |
Rok vydání: | 2020 |
Předmět: |
Filler (packaging)
Materials science business.industry 0211 other engineering and technologies Water supply 02 engineering and technology Engineering (General). Civil engineering (General) 01 natural sciences 010305 fluids & plasmas Metal visual_art 0103 physical sciences visual_art.visual_art_medium 021108 energy Composite material TA1-2040 business |
Zdroj: | MATEC Web of Conferences, Vol 315, p 03002 (2020) |
Popis: | The design of cooling tower`s filler unit, consisting of inclined-corrugated contact elements, and made of polymer material, is developed and described in this research paper. The experimental studies were conducted to determine the efficiency of cooling the circulating water in the proposed cooling tower. The authors obtained the results of evaluating the heat-mass transfer efficiency coefficient of cooling tower, when changing the mass flow rates of liquid and gas phases. The research results showed that the highest efficiency of cooling the circulating water is observed at relatively low irrigation densities equal to 15-25 m3/(m2·h), while the heat-mass transfer efficiency of cooling tower achieves 72%.The use of non-metal materials as the main elements of cooling tower allows to abandon the use of chemical reagents against bacteria and microorganisms in favor of circulating water ozonation method. |
Databáze: | OpenAIRE |