Mitigating grid voltage harmonics using a line converter with active filtering feature
Autor: | Antti Tarkiainen, Riku Pollanen, Markku Niemela, Juha Pyrhonen |
---|---|
Rok vydání: | 2004 |
Předmět: | |
Zdroj: | Electrical Engineering. 88:97-107 |
ISSN: | 1432-0487 0948-7921 |
DOI: | 10.1007/s00202-004-0261-3 |
Popis: | A line converter equipped with an LCL-line filter is used as an active filter directly compensating grid voltage harmonics. The control of four individual grid voltage harmonics is implemented using an individual control of corresponding harmonic line currents. The knowledge of the grid impedance is essential to efficient control of the grid voltage harmonics. To overcome the problem of an unknown grid impedance an identification method is used. The method uses the converter control system to measure the grid impedance at selected frequencies. The active voltage harmonic cancellation is tested with a 19 kVA line converter by compensating background voltage distortion and distortion caused by a nonlinear load. |
Databáze: | OpenAIRE |