business.industry Protective relay Electrical engineering Energy Engineering and Power Technology Fault (power engineering) Line (electrical engineering) law.invention Electric power transmission Transmission line Relay law Electronic engineering Electrical and Electronic Engineering Digital protective relay Power-system protection business |
Zdroj: | IEEE Transactions on Power Delivery. 11:191-196 |
ISSN: | 0885-8977 |
DOI: | 10.1109/61.484016 |
Popis: | This paper describes the performance of the protection system used for the first commercially operated six-phase transmission line in the world-New York State Electric & Gas's 93 kV (phase to phase and phase to ground) line from Goudey Station to Oakdale substation (USA) during faults in the winter of 1993. The paper briefly describes the basics of the High-Phase Order Transmission Demonstration Project and the integration of available state of the art microprocessor based relays, with a programmable logic relay (designed for the protection of conventional three-phase systems) in a hierarchical six-phase protection system. The operation of the protection system during two faults on the line in January and February 1993 is reported. The modeling of the six-phase line in a conventional three-phase short circuit study program is also considered and a comparison between the measured and calculated fault currents is presented. |