Influence of platform screen doors on energy consumption of the environment control system of a mass rapid transit system: case study of the Taipei MRT system
Autor: | Shih-Cheng Hu, Jen-Ho Lee |
---|---|
Rok vydání: | 2004 |
Předmět: |
Chiller
Engineering Renewable Energy Sustainability and the Environment business.industry Environmental control system Cooling load Energy Engineering and Power Technology Energy consumption law.invention Fuel Technology Nuclear Energy and Engineering law Air conditioning Ventilation (architecture) Doors Electricity business Simulation |
Zdroj: | Energy Conversion and Management. 45:639-650 |
ISSN: | 0196-8904 |
DOI: | 10.1016/s0196-8904(03)00188-2 |
Popis: | This investigation studies how platform screen doors (PSD) affect the energy consumption of the environmental control system of a mass rapid transit (MRT) system in Taipei. The environmental parameter simulation was conducted using the subway environmental simulation (SES) program, while the associated air conditioning (A/C) cooling load was predicted with the carrier E20-II program. Results show that PSD can significantly decrease average and peak cooling load, thus reducing the capacity/size of cooling equipment and allowing the chiller cooling load to be abridged. However, electricity consumption by ventilation equipment increases notably when PSD are used, particularly the electricity consumption by the under platform exhaust (UPE) fan, and thus, ultimately, little difference exists in the overall energy consumption with and without UPE. |
Databáze: | OpenAIRE |
Externí odkaz: |