Plasma Density Measurements Using a Double Langmuir Probe in a Prototype Vaccuum ARC Fault Current Limiter

Autor: P. D. Pedrow, J. L. Shohet, L. M. Burrage
Rok vydání: 1981
Předmět:
Zdroj: IEEE Transactions on Power Apparatus and Systems. :2740-2745
ISSN: 0018-9510
DOI: 10.1109/tpas.1981.316367
Popis: Electric power systems could benefit from a device that would limit the magnitude of short-circuit current. A switched resistor fault current limiter requires a commutating switch capable of interrupting current without the benefit of a natural current zero. The unstable diffuse plasma discharge between electrodes in a cylindrical geometry might be capable of such a task but the phenomena involved in this discharge is not completely understood. To develop a detailed model of this unstable discharge, measurements of the plasma density as a function of position and time were made using a double probe. A maximum density of 5 x 1020 m-3 was measured 90 mm from the cathode of this diffuse copper vapor discharge in vacuum.
Databáze: OpenAIRE