Characteristics of a Corona between a Wiring Clamp(Dead End Clamp) and a Porcelain Insulator Used in a 154[kV] Power Receptacle

Autor: Sun-Bae Bang, Hyeong-Jun Choi, Jong-Min Kim, Han-Sang Kim, Un-Ki Han
Rok vydání: 2007
Předmět:
Zdroj: Journal of the Korean Institute of Illuminating and Electrical Installation Engineers. 21:57-63
ISSN: 1229-4691
DOI: 10.5207/jieie.2007.21.9.057
Popis: The occurrence of a corona is that electrical discharge due to the heterogeneity that occurs when an electrical field is concentrated in an electrode due to a cusp formed on said electrode. Wire treatment at the end of a 154[㎸] dead end clamp for end users accelerates the occurrence of corona, which in tum leads to power loss and noise. In this study, the characteristics of the corona which occurs between porcelain insulators and support clamps of overhead lines used in 154[㎸] power receiving facilities for end users were investigated. The corona, which cannot be identified by one common method, was measured utilizing a IN image carrera A risk assessment for fire damage and its status was suggested. The stress distribution of the electrical field by length of bare wire was suggested by means of the finite element method (FEMLAB). As a result, it was found to affect a porcelain insulators. These results can be utilized for the enhancement of clamp installation and safety in power facilities.
Databáze: OpenAIRE