Popis: |
In this paper, based on the choice of voltage level 500kV for large transformer differential protection of maloperation accident actually as an example, discusses how to improve the reliability and the transformer differential protection with the relationship between pressure test. Analysis found that in order to avoid the excitation transient exciting current transformer differential protection sparked the misoperation, on-site technical personnel in the differential protection setting calculation process, make use of data in conformity with the relevant parameters, rules and standards, familiar with differential protection, also need to understand the characteristics of transformer excitation transient exciting current high-voltage tests, the influence of characteristic more should fully exert the modern PC wave record device, instrument function can improve the actual effect of transformer differential protection. This factory for transformer differential protection for setting, protection greatly improves the reliability. This experience is worth popularizing. |