Popis: Pohang Accelerator Laboratory (PAL) started operation of an X-ray Free Electron Laser (XFEL) based on 10GeV linear accelerator in FY2015. For accurate temperature control of the various XFEL accelerator devices, a low-conductivity water (LCW) cooling system were installed. The LCW pump station generates LCW controlling the temperature variation within ±0.1°C. The LCW is supplied to klystrons including modulators and various control devices. On the other hand, the precision temperature controlled water to minimize temperature variation down to ±0.02°C. This water is supplied to accelerating columns, wave guide and SLED. Therefore, this paper shows the design, construction and operation of the LCW cooling system.