Carrier Frequency Harmonics Generated By HVDC Conversion
Autor: | L. Haglof, D. J. Melvold, P. Degn |
---|---|
Rok vydání: | 1980 |
Předmět: |
Engineering
Carrier signal business.industry General Engineering Electrical engineering Energy Engineering and Power Technology Inductor Capacitance Transmission line protection law.invention law Harmonics HVDC converter station Electronic engineering Electrical and Electronic Engineering business Transformer Voltage |
Zdroj: | IEEE Transactions on Power Apparatus and Systems. :564-572 |
ISSN: | 0018-9510 |
DOI: | 10.1109/tpas.1980.319702 |
Popis: | The operation of the Sylmar HVDC Converter Station has generated interference voltages in the carrier frequency range. Especially a 24 kHz oscillation has caused interference with carrier-type line protection in the ac system as well as with equipment in the station itself. It was shown that the 24 kHz oscillation was caused by a resonance between a RI-filter reactor and stray capacitances in the converter transformers. The comparison between digital simulations and measurements in the station gives a general indication of how complex a digitdl model of a converter station shall be for calculating interference voltages. Such calculationis are expected to be of increasing importance in the future. |
Databáze: | OpenAIRE |
Externí odkaz: |