Autor: |
M. Djurovic, N.M. Pekaric Nadj, R.M. Dimitrijevic, S.V. Nikolajevic |
Rok vydání: |
2002 |
Předmět: |
|
Zdroj: |
Conference Record of the 1996 IEEE International Symposium on Electrical Insulation. |
DOI: |
10.1109/elinsl.1996.549442 |
Popis: |
The paper describes a study of various cable termination constructions for medium voltage cross-linked polyethylene (MV XLPE) cables. A special device was used for electrical field measurements around the cable termination, which made it possible to monitor how stress relief materials with different relative permittivity, thickness of stress relief layer and placement of isolated or grounding embedded electrodes (EE) affect electrical stress grading. The results of measurements for each construction were examined by mathematical modeling based on the finite element method (FEM). Also, the influence of dielectric losses in the termination was considered when relative permittivity of the stress relief material is high. Finally, the selected constructions of cable termination were tested in service conditions with load cycling. |
Databáze: |
OpenAIRE |