Autor: |
Gordon R. Jones, L.T. Isaac, Joseph W. Spencer, W.B. Hall, J. E. Humphries |
Rok vydání: |
1999 |
Předmět: |
|
Zdroj: |
IEE Proceedings - Generation, Transmission and Distribution. 146:453 |
ISSN: |
1350-2360 |
DOI: |
10.1049/ip-gtd:19990331 |
Popis: |
Experimental results have been obtained about conditions within SF/sub 6/ puffer circuit breakers during and after the interruption of fault currents up to 45 kA peak using optical-fibre sensors based on chromatic modulation. The particular parameters measured with the optical-fibre sensors were the contact travel, the gas pressure in both the puffer piston chamber and the circuit-breaker tank, the radiative emission from the electric arc and the concentration of micron-sized particles produced by the arcing. The experimental results are compared where possible with theoretical calculations from a computational-fluid-dynamics computer package. The possible role of the particulate material in the longer-timescale conditions within the circuit-breaker tank is considered and the need for a better understanding of the particulate-material properties and formation is highlighted. |
Databáze: |
OpenAIRE |
Externí odkaz: |
|