Evaluation of Solar Fraction on a Solar Driven Dual Parallel Connected Ejector Cooling System
Autor: | Tawat Suriwong, Timeyo Mkamanga Maroyi, Sakda Somkun, Anan Pongtornkulpanich, Yahya Gaafar Abdella Mohammed |
---|---|
Rok vydání: | 2016 |
Předmět: |
geography
Engineering geography.geographical_feature_category Renewable energy technology business.industry Nuclear engineering Boiler (power generation) Mechanical engineering General Medicine Injector Inlet law.invention Solar air conditioning law Water cooling Working fluid business Monthly average |
Zdroj: | Applied Mechanics and Materials. 839:94-99 |
ISSN: | 1662-7482 |
Popis: | This present study reports results of performance evaluation of a solar-driven dual parallel-connected ejector (DPE) cooling system using the concept of solar fraction (SF). The experiments were conducted in July and August, 2015 from 09:00 to 16:00 hours at School of Renewable Energy Technology (SERT), Naresuan University, Thailand, with a solar collector area of 2.4 m2, auxiliary heater of 3 kW, operating at boiler pressure of 2 bar and using water as working fluid. Temperature was measured for inlet and outlet of solar collector. The results showed that the solar collector supplied about 24% of energy required to operate the system. The solar collector performance was 11% and the monthly average SF was 23.9% for July and 23.5% for August. |