Testing Electric Utility Smart Meters with High Harmonic Current Waveforms

Autor: Julia Codere, Shannon Edwards, Richard L. Steiner, Sumaya Sarwat, Thomas L. Nelson, Michael Farrell
Rok vydání: 2020
Předmět:
Zdroj: 2020 Conference on Precision Electromagnetic Measurements (CPEM).
DOI: 10.1109/cpem49742.2020.9191866
Popis: This paper describes the results from testing the accuracy of electric utility smart meters. The results compare the smart meter measurements of voltage and current waveforms of a fundamental 60 Hz frequency with energy usage that contains current signals with narrow spikes. The Fourier component analysis of the current spikes requires high harmonic frequency analysis. A separate, precision power analyzer was calibrated as the reference. The worst-case error of about 3% was measured for three similar model meters out of twelve meters, where the uncertainty was about 0.1%.