Mitigation of circuit breaker transient recovery voltages associated with current limiting reactors
Autor: | A. Sarshar, D.F. Peelo, R. Presta, P. Diamanti, J.H. Sawada, G.S. Polovick, R. Beauchemin |
---|---|
Rok vydání: | 1996 |
Předmět: |
Engineering
Transient recovery voltage business.industry Electrical engineering Energy Engineering and Power Technology Hardware_PERFORMANCEANDRELIABILITY Automotive engineering Current limiting Transient response Transient (oscillation) Electrical and Electronic Engineering Power-system protection business Circuit breaker Voltage Current limiting reactor |
Zdroj: | IEEE Transactions on Power Delivery. 11:865-871 |
ISSN: | 0885-8977 |
DOI: | 10.1109/61.489345 |
Popis: | BC Hydro and Hydro-Quebec utilize current limiting reactors on medium voltage distribution feeders to limit the magnitude of fault current. The reactors make a significant contribution to the severity of the transient recovery voltage experienced by feeder and bus circuit breakers on clearing feeder faults. Based on the conclusions of an investigation of actual circuit breaker failures while performing this duty, the mitigation of the transient recovery voltage associated with the reactors is described. |