Cooling of office buildings in cold climates using direct ground-coupled active chilled beams
Autor: | Taha Arghand, Jan-Olof Dalenbäck, Anders Trüschel, Saqib Javed |
---|---|
Rok vydání: | 2021 |
Předmět: |
060102 archaeology
Renewable Energy Sustainability and the Environment 020209 energy Nuclear engineering Borehole Thermal comfort 06 humanities and the arts 02 engineering and technology Chilled beam Setpoint Heat exchanger 0202 electrical engineering electronic engineering information engineering Water cooling Environmental science 0601 history and archaeology Internal heating Intensity (heat transfer) |
Zdroj: | Renewable Energy. 164:122-132 |
ISSN: | 0960-1481 |
DOI: | 10.1016/j.renene.2020.09.066 |
Popis: | This study investigates the use of a direct ground cooling system (DGCS) using active chilled beams for the cooling of office buildings in Sweden. The methodology of the study entails laboratory experiments to develop and validate a simulation model of the cooling system. The sensitivity of the input parameters, such as borehole heat exchanger (BHE) length, internal heat gains and room temperature set point, are studied with respect to BHE outlet fluid temperature and room thermal comfort. The results provide a practical insight into designing DGCSs with regard to borehole outlet fluid temperatures. The results also show that the thermal comfort criteria in the room are met by applying the DGCS even under the most critical design conditions of undisturbed ground temperature and internal heat gains. The sensitivity study quantifies the influence of the room temperature setpoint and internal heat gain intensity on the BHE length. The BHE outlet temperature level is more sensitive in shorter BHEs than in the longer ones, and BHE length and room temperature levels are highly correlated. Thus, the sizing of DGCS can benefit from a control system to allow the room temperature to float within a certain range. |
Databáze: | OpenAIRE |
Externí odkaz: |