Influence of Flue Gas Pattern Flow in Boiler Radiant Section on Heat Transfer

Autor: Branislav Jaćimović, Nikola Jaćimović, Srbislav Genić
Rok vydání: 2021
Předmět:
Zdroj: Journal of Thermal Science and Engineering Applications. 14
ISSN: 1948-5093
1948-5085
DOI: 10.1115/1.4051369
Popis: During the sizing of the radiant zone in boilers and furnaces, the most often used method is the Lobo-Evans model. This method is based on the perfect mixing model for flue gas flow inside the fire box, which represents a conservative or pessimistic flow pattern. This paper presents a different, optimistic model which is based on the plug flow for flue gas flow which results in the largest possible heat duty. The proposed model is given in two distinct forms—integral and numerical. As shown in the paper, the integral model results in small deviations with respect to the numerical model and, as such, is well suited for the engineering practice. Paper also presents an engineering approach to the calculation of the conductive heat transfer through the membrane wall, which is shown to be sufficiently accurate and simple for engineering calculations.
Databáze: OpenAIRE