FM Global Large-Scale Fire Sprinkler Testing

Autor: Jason A. Sutula, R. Thomas Long, Michael Kahn
Rok vydání: 2014
Předmět:
Zdroj: SpringerBriefs in Fire ISBN: 9781493910762
Popis: Two large-scale fire tests were conducted to evaluate the level of protection provided by a ceiling only sprinkler system. The performance objective was for the ceiling only sprinkler system to extinguish a large-scale rack storage fire of CUP commodity. The passing criteria for the test was that the fire must be nearly extinguished before the predicted time of significant battery involvement established for the Li-ion battery commodities in the reduced-commodity tests (see Sect. 5.1).