Popis: |
Two large-scale fire tests were conducted to evaluate the level of protection provided by a ceiling only sprinkler system. The performance objective was for the ceiling only sprinkler system to extinguish a large-scale rack storage fire of CUP commodity. The passing criteria for the test was that the fire must be nearly extinguished before the predicted time of significant battery involvement established for the Li-ion battery commodities in the reduced-commodity tests (see Sect. 5.1). |