Influence of Quadrature-Axis Reactance of Large Turbine Generator on Operation

Autor: Mikio Kakiuchi, Daisuke Hiramatsu, Junji Okumoto, Ken Nagakura, Toru Otaka, Masafumi Fujita, Yoichi Uemura, Shinji Uemoto, Imai Takehiko
Rok vydání: 2009
Předmět:
Zdroj: IEEJ Transactions on Power and Energy. 129:93-100
ISSN: 1348-8147
0385-4213
DOI: 10.1541/ieejpes.129.93
Popis: Two-pole large generators are extensively used in power utilities. Growing demand for electric power in recent years has led to substantial increases in the capacity of generators. In line with this trend, our company has manufactured two-pole turbine generators in the 900,000-kVA to 1,200,000-kVA classes. As the capacity of generators becomes larger, equivalent circuits are increasingly expected to improve their precision in estimating operation characteristics. The Park model has been widely used as an equivalent circuit model. The Park model with quadrature axis transient reactance is claimed to be useful for accurately estimating the load rejection characteristics of turbine generators. However, it is difficult to measure , few studies based on measured data have appeared. As one of the few examples, we have conducted a measured data on a 500,000-kVA-class generator. Recently, the authors obtained test data on of a 900,000-kVA-class generator. In this study, based on these data, we studied the effect of using the finite element method and a transient analysis program (EMTP-ATP). © 2011 Wiley Periodicals, Inc. Electr Eng Jpn, 177(3): 17–27, 2011; Published online in Wiley Online Library (wileyonlinelibrary.com). DOI 10.1002/eej.21099
Databáze: OpenAIRE