Popis: |
This paper investigates the use of structural damping in blast response calculations. In recently published literature, there are many examples of structural damping being used in computational models with little or no experimental or theoretical justification. The use of even small amounts of damping in computational models involving nonlinear plastic response can significantly influence the response calculations. For example, for a given blast loading, a reinforced concrete slab with only 48 kPa maximum capcacity and 25 percent of critical damping (a value typically recommended) will deflect the same as (i.e., provide the same level of protection as) a slab with 690 kPa maximum capacity and no damping. Clearly a fictitous damping term that provides as much as 93 percent of the resistance is problematic. Structural damping during plastic response cannot be clearly defined or verified experimentally. Therefore, the use of damping in plastic response calculations should be avoided. |