Accelerated aging of so2 switchgear seals

Autor: Paulo O. Fernandes, Vanderlei Ricardo Cruz, Helena M. Wilhelm, Leandro G. Feitosa, Fernando Wypych, Neffer Arvey Gomez Gomez, Mauricio Mattoso, Luiz Henrique Meyer
Rok vydání: 2016
Předmět:
Zdroj: IEEE Electrical Insulation Magazine. 32:21-27
ISSN: 0883-7554
DOI: 10.1109/mei.2016.7361100
Popis: Partial discharges in SF6-insulated electrical equipment generate gaseous and solid by-products. The gaseous by-products remain in the SF6 during operation, reducing its insulation and heat conduction capacities, and causing deterioration of solid material present in the equipment [1]–[3]. These by-products reduce the operational reliability of SF6-insulated equipment and increase the need for maintenance work [4]. It was shown in [5] that some by-products of SF6 may interact with the sealing materials of SF6-insulated equipment, leading to gas leaks. A CIGRE study [4] revealed that, between 1991 and 1998, 40% of failures in SF6-insulated high voltage equipment were caused by leaks. IEC 62271-303 [6] stipulates that SF6 gas leakage should not exceed 0.5% of the mass of the gas contained in the relevant equipment. Nevertheless, a series of surveys [7] found that the main failure modes of high voltage components in circuit breakers were due to small gas leaks. As a consequence, condition-based maintenance was introduced in the electrical utilities [8], [9] to alleviate the problems caused by gas leaks [10].