Simulation of the effect of the condensing temperature on the performance of a split AC with R-410a under constant cooling capacity
Autor: | Andriyanto Setyawan, Ade Suryatman Margana, Tandi Sutandi, Faldian |
---|---|
Rok vydání: | 2018 |
Předmět: | |
Zdroj: | AIP Conference Proceedings. |
ISSN: | 0094-243X |
DOI: | 10.1063/1.5049965 |
Popis: | This paper analyzes the performance of a split air conditioner at various condensing temperature under the constant cooling capacity. The nominal capacity of the air conditioning unit is 5.06 kW and the refrigerant is R-410a. The simulation shows that the increase of the condensing temperature causes the unit require the higher volumetric and mass flow rate of refrigerant to maintain the constant cooling capacity. The condenser capacity and the work of compression increase as well. On the other hand, the refrigerating effect decreases so that the overall performance of the air conditioning unit decreases. |