Autor: |
Whei-Min Lin, Chang-lin Lee |
Rok vydání: |
2007 |
Předmět: |
|
Zdroj: |
TENCON 2007 - 2007 IEEE Region 10 Conference. |
DOI: |
10.1109/tencon.2007.4428790 |
Popis: |
There is a tendency for excitation control system to upgrade to the digital-based type, with the functions and benefits discussed in (September 1997). New computer models had been developed for representation of the renewal digital-based excitation system in transient stability studies after IEEE Std 421.5 [2] adoption. This paper provides a guide line for replacement of the excitation control system from analog-based to digital-based. These techniques had been used on large steam generator excitation systems of a nuclear power plant in Taiwan. An optimal set of excitation system settings plays a very important role in power system stability. This paper will address the parameters setting and field tuning method for a self-excited exciter rewired to be separated-excited with station auxiliary power. The performance indices were also checked and compared with IEEE Std 421.2[3]. |
Databáze: |
OpenAIRE |