Autor: |
Vladimir Černicin, Milena Otović, Nenad Mitrović, Srbislav Genić, Srđan Otović, Milan I. Antić, Uroš Milovančević |
Rok vydání: |
2020 |
Předmět: |
|
Zdroj: |
Proceedings of the 51st International HVAC&R Congress and Exhibition. |
DOI: |
10.24094/kghk.020.51.1.11 |
Popis: |
On the hitherto installed chillers/rooftopunits/dry coolers and air coolers, a significant improvement in cooling wasnoticed in the summer mode when the pipe bundle is sprayed with water. Tests have been performed on systems that produce water mist (micron-sized water droplets), which are formed by spraying water under high pressure through the nozzles/nozzle openings. When a drop of micron-sized water comes in contact with warm air, it evaporates very quickly, absorbing a certain amount of heat, which results in cooling the air. This improves the operation of the cooler in critical periods when the ambient air temperatureis very high. The aim of the test is to determine the im-provement of the cooler operation under operating conditions with the application of the described system in relation to the operating mode without water spraying (dry operating mode). |