Partial Non-Zero Fault Response of Grid-Connected DFIG
Autor: | G. Pannell, Shady Gadoue, David J. Atkinson, Bashar Zahawi |
---|---|
Rok vydání: | 2018 |
Předmět: |
Computer science
Rotor (electric) 020209 energy 020208 electrical & electronic engineering Induction generator Hardware_PERFORMANCEANDRELIABILITY 02 engineering and technology Fault (power engineering) Grid Turbine Power (physics) law.invention Generator (circuit theory) law Control theory 0202 electrical engineering electronic engineering information engineering Voltage |
Zdroj: | 2018 XIII International Conference on Electrical Machines (ICEM). |
DOI: | 10.1109/icelmach.2018.8506930 |
Popis: | This paper presents a detailed experimental study of wind turbine DFIG response to non-zero grid faults that may occur at a considerable distance from the generator. An analytical solution of the generalized DFIG machine equations operating under non-zero fault conditions is developed in which the fault response is separated into three components: a natural response that describes zero voltage behavior, a component describing the retained voltage behavior and the forced response corresponding to the applied rotor voltage via the rotor-side power converter. The DFIG system fault response is examined experimentally using a 7.5kW test facility detailing example of a 500ms, 15% fault. |
Databáze: | OpenAIRE |