Popis: |
High voltage tests were performed on a 5-m long prototype triaxial HTS cable (supplied by Ultera) at ORNL in preparation for installation of a 200-m HTS cable of the same design at the AEP utility substation in Columbus, Ohio. The triaxial design comprises three concentric phases and shield around a common former with the phase to phase dielectric at cryogenic temperature. Advantages of this design include increased current density, a reduced amount of HTS tape needed, and reduced heat load. The phase to phase voltage will be 13.2 kVrms (7.6 kVrms to ground). Preliminary testing was done on half-scale and full-scale terminations which successfully passed AC withstand, partial discharge, and impulse tests. High voltage tests conducted on the 5-m cable with the cable straight and after bending 90 degrees were ac withstand to 39 kVrms, partial discharge inception, and a minimum of 10 positive and 10 negative lightning waveform impulses at 110 kV. Phase to phase insulation was tested by applying high voltage to each phase one at a time with all the other phases grounded. Partial discharge data will be presented. The 5-m prototype triaxial HTS cable passed all the HV tests performed, with a PD inception voltage significantly above the required voltage. |