This paper purposes a short circuit current estimation method using phasor measurement unit (PMU) measurements (synhcrophasors, hereafter called as phasors) of voltages and currents obtained during normal load variation. The method follows the basic concept of representing the source side of power system by an equivalent circuit with a voltage behind back impedance and employs a set of voltage and current phasors measured at substations over a certain period. In order to improve an accuracy of the proposed estimation method, the concept of using a difference between the two consecutive phasors is introduced. Furthermore, to make the method applicable to a real world system, the estimation process is augmented by implementing a reference phasor concept to remove the effects of system wide frequency variations and a filtering process to filter out the outlier phasors. Finally, the validity and effectiveness of the purposed methods were checked and confirmed using field tests. |